Kidde Fire Extinguisher Recall 2017

If you have any Kidde fire extinguishers in your Maryland, DC, or Virginia business, your equipment could be affected by a recent recall issued by the manufacturer in November 2017. The recall stems from reports Kidde has received that several of their fire extinguisher models are unsafe or ineffective to use in a fire emergency. Check your extinguishers now and use the information below to help you determine if you should take action.

If you are located in Maryland, Virginia, or Washington, DC and need to replace your fire extinguishers, contact us online now.

Why Is Kidde Recalling Fire Extinguishers?

Certain models of Kidde fire extinguishers with plastic handles reportedly fail to discharge properly in a fire emergency because the nozzle becomes clogged. Some reports also indicate that the nozzle may detach with enough force to cause injury on impact.

A total of 391 reports have been filed with complaints of failed or limited discharge or nozzle detachment. One incident in 2014 resulted in the death of a civilian when emergency responders couldn’t douse a car fire because the recalled Kidde extinguisher they attempted to use became clogged. In total, 16 injuries, 91 incidents of property damage, and the fatality described here spurred the Kidde recall, which was announced on November 2, 2017.

Is My Kidde Fire Extinguisher Affected?

The recall applies to about 37.8 million extinguishers in the US, 2.7 million extinguishers in Canada, and 7,000 extinguishers in Mexico. While there’s no guarantee that all of these units are unsafe, Kidde has made the responsible decision to recall all potentially affected extinguishers. Some of the models included in this recall were previously discontinued and recalled in March 2009 and February 2015.

The Kidde recall applies to two fire extinguisher styles:

  • Plastic handle extinguishers: If you have ABC or BC Kidde fire extinguishers manufactured between 1973 and 2017 that have plastic handles, they may demonstrate the problems listed above. Check the model number on the side of your fire extinguisher and compare it to the chart of recalled models on the Consumer Product Safety Commission website. In total, 134 plastic handle models are affected.
  • Push-button Pindicator extinguishers: If you have Kidde Pindicator fire extinguishers manufactured between 1995 and 2017, they may be affected by the recall. These units are no-gauge push-button models in red and white canisters with red or black nozzles designed for use in kitchens and personal watercrafts. You can find the exact models on the CPSC website. In total, eight Pindicator models are affected.

Before the recall, these Kidde fire extinguishers were sold at various outlets. You may have purchased yours at:

  • Menards
  • Montgomery Ward
  • Sears
  • The Home Depot
  • Walmart
  • Other department, home, and hardware stores
  • Amazon.com
  • ShopKidde.com
  • Other online retailers

What to Do After the Recall

Kidde is instructing consumers to replace all recalled extinguishers. As a Kidde authorized dealer, Guardian Fire Protection is the perfect source for replacing your fire extinguishers. We can supply you with a safe replacement from Kidde or install a new extinguisher from another brand. We can also help you dispose of the recalled unit safely.

Fire Extinguisher Sales in Maryland, Washington, DC & Virginia

With over 30 years of experience delivering fire extinguisher sales to our customers, our team can be trusted to provide you with quality products at a great price. If you discover that your fire extinguishers are affected by the Kidde recall, please contact us online or call 301-861-0972 to begin the replacement process in the DMV area.

Guardian Performs with ServiceTrade

Providing faster, smarter, and more efficient fire protection

Learn more here

Contact Us
Let us know how we can help you
and a Fire Pros representative
will contact you within 24 hours.
Let’s TALK +
Click here
Hide Form -
Fire Pros Performs with ServiceTrade

Providing faster, smarter, and more efficient fire protection

Learn more here

Local Reviews

Fire Pros, LLC Rated 4.9 out of 5 stars based on 3670 customer reviews

Map of Ann Arbor, MI

Nice guys




Review of Fire Pros, LLC

Respectful and kind


Map of Troy, MI

Service manager




Review of Fire Pros, LLC


Map of Ann Arbor, MI

Another Portion of our Required Inspections




Review of Fire Pros, LLC

Staff was on time and friendly. Performed the work without incident and communicated well when they were finished.


Map of Bay City, MI

Great Service




Review of Fire Pros, LLC


Map of Dearborn, MI

Great Service




Review of Fire Pros, LLC

Professional and knowledgeable


Map of Detroit, MI

Fire Extinguisher Inspections




Review of Fire Pros, LLC

Professional and efficient.


Map of Dearborn, MI

Area Coach




Review of Fire Pros, LLC

Fantastic job! Great guys!


Map of Livonia, MI

Great Service, very polite and informative




Review of Fire Pros, LLC

Good experience, send again


Map of Bay City, MI

Building Manager




Review of Fire Pros, LLC

An excellent tech


Map of Grand Rapids, MI

No Problems




Review of Fire Pros, LLC


Excellent service




Review of Fire Pros, LLC

Great customer service. Excellent service.


Great Service, great technician




Review of Fire Pros, LLC

It was a pleasure to work with Sean!!!!!!!


Very good experience over the years.




Review of Fire Pros, LLC

Brandon Foote is very kind, patient, friendly and knowledgeable


Jared was very informative and updated me on all that needed to be done




Review of Fire Pros, LLC


Great service and Professionalism!




Review of Fire Pros, LLC

The technicians who came out, were very friendly, knowledgeable and helpful!


Dave was prompt in getting the inspection completed and docs over to me




Review of Fire Pros, LLC

i rec'd a call from Dave informing me the inspection was completed. He gave me a quick run down of the deficiencies. He had the inspection report in my emails before I could complete my notes on the file


New door magnet




Review of Fire Pros, LLC

Ron and Dennis were great as usual. Any problems they faced they overcame with professionalism. They did a great job.


Very helpful




Review of Fire Pros, LLC


Great service




Review of Fire Pros, LLC


Pastor




Review of Fire Pros, LLC


Mike R.

Mike R.

NAC 1 BOOSTER PANEL BY FACP: Batteries in NAC 1 panel are due for replacement due to age. They are (2) 12V 7AH batteries. - repair

Near W Grand River Ave, Williamston, MI 48895
Mark S.

Mark S.

Near Dobry Dr, Sterling Heights, MI 48314
William S.

William S.

Wet: Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire. NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 to inspect for the presence of foreign organic and inorganic material. Wet: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. Check is in the basement, next to the bathroom, up in the floor joist. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Wet: Add the missing spare sprinkler heads in the spare headbox. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities having 300-1000 sprinklers – minimum of 12 spare sprinklers

Near Front Ave NW, Grand Rapids, MI 49504
Tyler H.

Tyler H.

Mike Price just called- said the panel has been beeping since we left.

Near Danvers Ct SE, Kentwood, MI 49512
Mike R.

Mike R.

Heat Detectors above Reception Desk and in Directors office are not tied into system and require removal or repair. Areas are currently covered by smoke detectors. - repair Heat Detectors throughout (4) require replacement due to age/condition. Detectors reflect Manf Dates from 1983 to 1999 4 - System Sensor 135 degree fixed / ROR detectors - repair Phone line 1 has voltage, no dial. Phone line 2 has heavy static on line. Phone lines are in disrepair and have been a continuing issue per the Director. Recommend installation of Cellular Communicator at location. - repair This quote is for the repairs and to add cellular communication to the fire alarm panel .

Near N Lilley Rd, Canton, MI 48187
David H.

David H.

Near Thomas Rd, Ann Arbor, MI 48108
Alex H.

Alex H.

Near Dequindre Rd, Madison Heights, MI 48071
Art L.

Art L.

Portable Extinguishers Inspection

Near E Paris Ave SE, Grand Rapids, MI 49546
Tyler H.

Tyler H.

Annual Fire Alarm Inspection Edwards fire alarm panel, 3 booster panels, 15 initiating devices, 25 indicating devices

Near Brown St SE, Grand Rapids, MI 49507
Robert G.

Robert G.

Near Smith Rd, Fowlerville, MI 48836
Jared J.

Jared J.

Portable Extinguishers and Fire Hose Inspection

Near Farmington Rd, Farmington Hills, MI 48334
George S.

George S.

Near E Scripps Rd, Orion charter Township, MI 48360
Brandon  F.

Brandon F.

Completed puff test and relocated pull station per fire Marshall request.

Near E Grand River Rd, East Lansing, MI 48823
William S.

William S.

Wet Stairwell next to Community Room B Riser: Remove and replace the outdated gauge. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years Wet Stairwell next to Community Room B Riser: Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire (8' ladder needed). NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 to inspect for the presence of foreign organic and inorganic material. Wet Stairwell next to Community Room B Riser: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

Near Jupiter Ave NE, Plainfield charter Township, MI 49306
Art L.

Art L.

Industrial/Dry Chemical Suppression Repair

Near 29th St SE, Grand Rapids, MI 49512
Sean W.

Sean W.

Near Health Dr SW, Wyoming, MI 49519
John  R.

John R.

Near Wiersma St NE, Cedar Springs, MI 49319
Art L.

Art L.

Portable Extinguishers Inspection

Near W Main St, Lowell, MI 49331
Mark S.

Mark S.

Near N Dawson St, Sandusky, MI 48471
George S.

George S.

Near Giddings Rd, Orion charter Township, MI 48359
David H.

David H.

Near Washtenaw Ave, Ann Arbor, MI 48104
Art L.

Art L.

Emergency / Exit Lights and Portable Extinguishers Inspection

Near 44th St SE, Kentwood, MI 49512
John  R.

John R.

Near Griswold St, Hart, MI 49420
Sean W.

Sean W.

Near Central Blvd, Hudsonville, MI 49426
Mark S.

Mark S.

Near N Dawson St, Sandusky, MI 48471