1-800-968-2871
Schedule Service Today

 

1-800-968-2871
Contact Us
Let us know how we can help you and a Fire Pros representative will contact you within 24 hours.

Inspection Code Requirement FAQs

If you have any questions on fire protection inspection code requirements, our team at Fire Pros has put together some answers provided by the National Fire Protection Association (NFPA).

If you have any further questions regarding inspection code requirements that are not answered below, feel free to contact our fire protection experts online or by calling (800)968-2871.

If an existing fire protection system is found to contain installation deficiencies, where in the standard does it require corrective action?

NFPA 25 is not intended to address installation deficiencies. In fact, Section 1.1 states, “Where a system has not been installed in accordance with generally accepted practices, the corrective action is beyond the scope of the standard.”

What type of tests are required when a fire protection system component is replaced or rebuilt?

NFPA 25 requires testing in accordance with the original acceptance test for that component or subsystem. This information can be found in the installation standard for the type of system involved.

Is fire protection system investigation required every five years?

There are two activities related to obstructions that require attention. The first is more of an “inspection” that is to be conducted every five years. While the sprinkler system is shut down for the purpose of internal valve inspections, the flushing connection at the end of one crossmain and a single sprinkler at the end of one branchline must be removed and the inside of the piping is then “inspected” for the presence of organic and inorganic material.

The second investigation is more comprehensive and must be conducted when any of the 14 conditions listed in Section 13.2.2 of NFPA 25 apply. This more comprehensive obstruction “investigation” is conducted by internally examining the following four points in a system: system valve, riser, crossmain, and branchline. It is only required when one of the 14 problems listed in Section 13.2.2 is present. This obstruction investigation is not a routine procedure; it is only needed when a problem exists. If any obstructing material is found, a complete flushing program must be conducted to remove any remaining obstructing material.

Are bags (paper or plastic) acceptable to protect fire sprinklers from accumulation of dust or other contaminants?

Bags are only permitted when sprinklers are protecting spray coating areas. Plastic bags must have a minimum thickness of 0.003 in. (0.076 mm) or small paper bags may be used.

Sprinklers protecting areas other than spray coating hazards are not permitted to have bags placed over the sprinklers.

How many sprinklers must be removed from a system for testing?

Section 5.3.1.2 requires that one percent (or no less than four) be removed and submitted to a testing laboratory for evaluation. If a system contains 500 sprinklers for example (400 upright and 100 pendent), then a total of eight sprinklers must be removed; 400X.01=4 and 100X.01=1 (but not less than 4).

When replacing sprinklers in a system, is it necessary to perform a hydrostatic test?

It is sometimes a common practice to hydrotest a system without sprinklers installed, i.e., with ½” plugs installed in the bottom of a drop to a pendent sprinkler and then install the sprinkler after final adjustment of the drop once the finished ceiling is installed. Both standards are silent on this issue.

Our suggestion is to consult the local fire marshal to determine what he/she will accept. In most cases, when replacing sprinklers only and not modifying the pipe, a hydrostatic test is not required.

Do standpipe systems require a periodic hydrostatic test?

Yes. However, only dry standpipe systems such as those found in a parking structure for example, must be tested every five years. The hydrotest is required to verify piping integrity. Wet systems do not need to be routinely hydrotested since leaks in the pipe are readily apparent.

Is water near the baseplate of the pump normal or do I have a leak?

A small amount of water in the baseplate drain is normal. This water should be dripping from the packing glands. The packing glands on the pump must be kept wet for proper lubrication (about one drop per second). Never adjust the packing gland to stop the dripping of water. To do so will prevent lubrication and will result in the destruction of the packing gland.

During the annual test of our fire pump, it was noted that pump performance was slightly less at peak flow than the results obtained during the original acceptance test. Is this a problem?

This may not be a problem. First, you should verify that all valves on the suction side of the pump and in the test header are open fully. Some decrease in performance can be expected due to slight wear of the pump or its components, but this is normal. The annual test is intended to ensure that the pump is capable of supplying the maximum system demand. The test results from the annual test are not required to meet the original pump curve as in the original acceptance test.

When is a main drain test required?

A main drain test is required annually or any time the water supply control valve is closed, which includes any time a system undergoes maintenance or repair. This test is essential to ensure that the water supply valve is fully open. Sprinkler systems perform exceptionally well. However, when they do fail, the major cause of failure (35% of the cases reported to NFPA) is that the water supply valve was closed, thus the verification of an open water supply valve cannot be overemphasized. The annual test frequency is a minimum requirement; NFPA 25 permits more frequent testing if desired.

Contact Us
Let us know how we can help you
and a Fire Pros representative
will contact you within 24 hours.
Let’s TALK +
Click here
Hide Form -
Fire Pros Performs with ServiceTrade

Providing faster, smarter, and more efficient fire protection

Learn more here

Local Reviews

Fire Pros & Fire Systems of Michigan Rated 4.9 out of 5 stars based on 3956 customer reviews

Map of East Lansing, MI

Quick turnaround




Review of Fire Pros & Fire Systems of Michigan


Map of Wayne, MI

maintenance dir.




Review of Fire Pros & Fire Systems of Michigan


Map of Warren, MI

The service was great! Over and above!




Review of Fire Pros & Fire Systems of Michigan

Mark went over and above helping us fix the initial issue and also a secondary issue that has been plaguing us. He was friendly, fast, and extremely knowledgeable. Loved the whole experience.


Map of Livonia, MI

Great Service!




Review of Fire Pros & Fire Systems of Michigan

Jared with Fire Pros has always done a great job for us. 100% recommend


Map of Kalamazoo, MI

smooth and fast




Review of Fire Pros & Fire Systems of Michigan


Map of West Bloomfield Township, MI

Hard worker , dedicated to his craft , showed concern about the situation and circumstance , feel very comfortable with Technician




Review of Fire Pros & Fire Systems of Michigan

Mark was concerned about my problem , called the next day to see how things were


Map of Climax, MI

Inventory Facilities Manager




Review of Fire Pros & Fire Systems of Michigan

John gets the job done in a timely manner. He is also very thorough.


Map of Dearborn, MI

Friendly and professional know what they were doing.




Review of Fire Pros & Fire Systems of Michigan

Satisfied


Map of Wayne, MI

maintenance dir.




Review of Fire Pros & Fire Systems of Michigan


Map of Troy, MI

Great service




Review of Fire Pros & Fire Systems of Michigan


GREAT SERVICE!




Review of Fire Pros & Fire Systems of Michigan

They are very professional and this experience was a great one. They explain what they've done, includes pictures and if you need any further help, questions with equipment, extinguisher's, etc they are very knowledgeable.


great service




Review of Fire Pros & Fire Systems of Michigan


Program Manager




Review of Fire Pros & Fire Systems of Michigan

Very professional, personable and answered questions well if asked.


great service




Review of Fire Pros & Fire Systems of Michigan


Great service.




Review of Fire Pros & Fire Systems of Michigan

Great company for your service needs.


Program Manager




Review of Fire Pros & Fire Systems of Michigan

he did a great job


Great guys




Review of Fire Pros & Fire Systems of Michigan

Great


Great customer service




Review of Fire Pros & Fire Systems of Michigan

So friendly, knowledgeable and speedy!


Eduardo Arredondo doing a great job.




Review of Fire Pros & Fire Systems of Michigan


great service but high price




Review of Fire Pros & Fire Systems of Michigan

very friendly ,knowable about his job, and does not waste time


William S.

William S.

Sprinkler Inspection

Near W State St, Hastings, MI 49058
William S.

William S.

Sprinkler Inspection

Near Health Dr SW, Wyoming, MI 49519
Alex H.

Alex H.

Near Northpointe Blvd, Utica, MI 48315
William S.

William S.

Sprinkler Inspection

Near Burlingame Ave SW, Wyoming, MI 49509
Mark S.

Mark S.

Near Calhoun St, Dearborn, MI 48126
Alex R.

Alex R.

Completed annual Fire Extinguisher inspection for 2022

Near W Michigan Ave, Ypsilanti, MI 48197
Terrence  J.

Terrence J.

Sprinkler Inspection Annual Sprinkler Inspection

Near Charles H Orndorf Dr, Brighton, MI 48116
William S.

William S.

Sprinkler Inspection

Near Wealthy St SE, Grand Rapids, MI 49506
Ron  R.

Ron R.

Near Nathan's Wy, Grand Haven, MI 49417
David H.

David H.

Near E Oakland Ave, Lansing, MI 48906
Art L.

Art L.

Portable Extinguishers Service Call

Near Market Ave SW, Grand Rapids, MI 49503
Robert G.

Robert G.

Near Allen Rd, Woodhaven, MI 48183
Brandon  F.

Brandon F.

Completed fire extinguisher inspection

Near Cascade Rd SE, Grand Rapids, MI 49546
David H.

David H.

Near Turf Ln, East Lansing, MI 48823
Robert G.

Robert G.

Near E River Rd, Grosse Ile Township, MI 48138
David H.

David H.

Near Jomar Ct, Lansing, MI 48917
Mike R.

Mike R.

Fire Alarm Inspection- 110v FACP in basement laundry room. (6) mp's (3) Horns

Near Clyde Park Ave SW, Wyoming, MI 49509
Terrence  J.

Terrence J.

Sprinkler Inspection Annual Sprinkler System Inspection (1 wet system) 5-Year Internal Due: 2024 FDC Hydro Due: 2024

Near Family Dr, Milford Charter Township, MI 48381
Mike R.

Mike R.

This quote is for an alarm tech to come out and re-install 5 speaker strobes in new ceiling tiles in the main entrance. There is a Wall speaker strobe above the ceiling that needs to be spliced through. Also turn down speakers on the devices the area is open now and doesn't need to be so load. This quote does not include permits if for some reason that its needed there will be an additional quote.

Near 44th St SW, Wyoming, MI 49519
Art L.

Art L.

Kitchen Suppression Inspection

Near Chicago Dr SW, Wyoming, MI 49509
Art L.

Art L.

Portable Extinguishers and Emergency / Exit Lights Inspection

Near Front Ave NW, Grand Rapids, MI 49504
David H.

David H.

Near 32nd St SE, Grand Rapids, MI 49548
Mike R.

Mike R.

This quote is for an alarm tech to come out and re-install 5 speaker strobes in new ceiling tiles in the main entrance. There is a Wall speaker strobe above the ceiling that needs to be spliced through. Also turn down speakers on the devices the area is open now and doesn't need to be so load. This quote does not include permits if for some reason that its needed there will be an additional quote.

Near 44th St SW, Wyoming, MI 49519
Mark S.

Mark S.

Near Dixie Hwy, Clarkston, MI 48348
Terrence  J.

Terrence J.

Sprinkler Inspection Annual Fire Sprinkler System Inspection - Boiler Room Deficiency: Pressure gauges are outdated. Deficiency: There is no evidence of five-year internal pipe investigation Deficiency: Sprinkler heads are outdated and will be more practical to have them be replaced.

Near Harper Ave, Harper Woods, MI 48225